PAW4504-V Integrated de 4 zone Unit - 500W
PAW4504-V Integrated de 4 zone Unit - 500W
PAW4504-V Integrated de 4 zone Unit - 500W
Features:
- Audio rated power: 500 W freely distributed between the zones up to a maximum of 250W within a single zone.
- 4.3” touch screen back-lighted display for alert & evacuation on zone selection, levels adjustment, settings and failure visualization.
- Fireman’s monitored microphone on the front panel.
- Sending of EVACUATION and ALERT pre-recorded messages.
- 7 monitored inputs, each of which is configurable for the playback or either evacuation or alert messages, programmable for each zone, or for reset of the messages.
- 1 music input for sound sources.
- 1 auxiliary input for external sound sources
- 3 configurable relay output.
- Double output A+B per zone.
- Secure front-panel button for operating the emergency system complete with LED indicator.
- Front-panel reset button.
- Possibility to source either BGM or paging announcements from microphone units.
- Possibility of connecting 16 paging units PMB106-G, PMB112-G
- Possibility to connect up to 4 remote emergency microphone units PMB132/12-V or as alternative up to 2 touch screen emergency units TSB8500-V
- Possibility of interconnecting up to 6 x PAW4500-VES units
- EN54-4 certified internal battery charger for 24 Vdc power supply (batteries not included).
Specifications:
MODEL |
PAW4502-V |
PAW4504-V |
PAW4506-V |
Rated audio output @230VAC *typical distortion at 25 W 0,025% |
500 W / D=2,5%* |
||
Rated audio output @24VDC *typical distortion at 25 W 0,025% |
400 W / D=10%* |
||
Display |
4.3” , backlit with touch screen, 480x272 pixels |
||
N° of PAW4500-VES/x per system |
Max 6 (ID 0 to 5) |
||
N° of zones/amplifiers |
2 |
4 |
6 |
Inputs |
|||
Emergency microphone • Sensitivity / Impedance • Frequency response • S/N ratio |
Balanced XLR-F on the front door Signal level: 20 mV / 10 kΩ 60 ÷20.000 Hz 72 dB |
||
Paging units (DESK) • Sensitivity / Impedance • Frequency response • S/N ratio |
1 off Rj45 for paging units (PA) Signal level: max. 1400 mV / 85 kΩ 60 ÷20.000 Hz 83 dB |
||
Emergency units (EMG. DESK) • Sensitivity / Impedance • Frequency response • S/N ratio |
1 off Rj45 for emergency microphone stations Signal level: max. 1400 mV / 85 kΩ 60 ÷20.000 Hz 83 dB |
||
AUX (LINE-VOX) • Sensitivity / Impedance • Frequency response • S/N ratio |
Balanced with terminals (HOT-COM-GND) Programmable in ON / OFF / VOX with A.P.T. modes Precedence input with contact closing activation 134 mV / 31 kΩ 90 ÷ 20.000 Hz 81 dB / 85 dBA |
||
MUSIC • Sensitivity / Impedance • Frequency response • S/N ratio |
Balanced with terminals (HOT-COM-GND) 134 mV / 31 kΩ 90 ÷ 20.000 Hz 81 dB / 85 dBA |
||
Outputs |
|
|
|
Constant voltage outputs With double lines (A/B) One zone output can be configured as a standby for the others. |
2 zones for 100V lines Minimum 40 Ω |
4 zones for 100V lines Minimum 40 Ω |
6 zones for 100V lines Minimum 40 Ω |
LINK • Output level / Impedance • Sensitivity / Input impedance |
2 off Rj45 for connection with another PAW4500-VES unit 1 V / 400 Ω 3600 mV / 3 kΩ |
||
Emergency controls • Controlled inputs CONT. IN • Outputs R1, R2, R3 |
Programmable for normally active or normally inactive state 7 off inputs with diagnostic 3 relays for signalling, state of emergency and faults, N.O-N.C-Exchange state |